Load Characteristic Model: MOTORW
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0 < Tpo < Mult*TimeStep then Tpo = Mult*TimeStep
- If 0.0 < Tppo < 0.5*Mult*TimeStep then Tppo = 0, ElseIf 0.5*Mult*TimeStep < Tppo < Mult*TimeStep then Tppo = Mult*TimeStep
- If H < 0.01 then H = 0.01.
- Pul: This is a normalized value, thus check if greater than 1, or less than 0; this catches a user ending a percentage value but do not autocorrect the value.
- If Lp > 0.4*Ls then Lp = 0.4*Ls
- If Lpp > Lp then Lpp = Lp
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters:
| Mbase | MBase: MBase of Load Model |
| ApplyToConstantPowerOnly | 0 means it applies to all, 1 means it applies to only the constant power part of the load |
| Pul | Fraction of constant-power load to be represented by this motor model (between 1.0 and 0.0) |
| Ls | Synchronous reactance |
| Lp | Transient reactance |
| Ra | Stator resistance, p.u. |
| Tpo | Transient rotor time constant |
| H | Inertia constant, sec. |
| D | Damping factor, p.u. |
| VT | Voltage threshold for tripping (default = 0), p.u. |
| TV | Voltage trip pickup time (default = 999), sec. |
| Tbkr | Circuit breaker operating time (default = 999), sec. |
| Acc | Acceleration factor for initialization |
| Lpp | Sub-transient reactance, p.u. |
| Tppo | Sub-transient rotor time constant, sec. |
| ndelt | Time step subdivision factor. |
| wdelt | Speed threshold for subdividing time step, p.u. |